kW to Amps: Calculator, Formulas and Generator Sizing Chart

To convert kW to amps, multiply kW by 1,000 and divide by the voltage times the power factor. For three-phase, also divide by √3 (1.732). A 500 kW load at 400 V three-phase and 0.8 power factor draws about 902 A. Use the calculator below for your own numbers, then check the generator sizing chart for common ratings from 20 kW to 2 MW.

Getting this conversion right is what keeps a correctly specified generator from feeding an undersized cable, breaker or switchboard. The relationships are fixed. What changes is whether the system is single-phase, three-phase or DC, and what power factor applies.

kW to Amps Formulas: Single-Phase, Three-Phase and DC

Three formulas cover almost every case. In each one, P is real power in kW, V is voltage in volts, PF is power factor, and I is current in amps.

System Formula Notes
Single-phase AC I = P × 1,000 ÷ (V × PF) V is the line voltage across the load
Three-phase AC I = P × 1,000 ÷ (√3 × V × PF) V is line-to-line; √3 = 1.732
DC I = P × 1,000 ÷ V No power factor, no phase

If you already know kVA, skip power factor. Single-phase: I = kVA × 1,000 ÷ V. Three-phase: I = kVA × 1,000 ÷ (√3 × V). The power factor is already inside the kVA figure. See our kW to kVA conversion table for quick conversions between real and apparent power.

Which Power Factor Should You Use?

Use the number on the nameplate or datasheet. For generator sets the standard rating is 0.8 lagging, so 0.8 is the default in this guide and in the tables below. Resistive loads such as heaters and incandescent lighting sit close to 1.0. Motor-driven plant runs well below 1.0, so read the nameplate.

The same kilowatts draw more current as power factor falls. At 0.7, a load draws about 14 percent more amps than at 0.8. Do not assume 1.0 for motors, crushers, pumps or compressors.

Worked Examples at Common Voltages (PF 0.8)

Each example uses the formula above with a 0.8 power factor. Three-phase voltages are line-to-line.

Voltage System Load Calculation Current
120 V Single-phase 2 kW 2,000 ÷ (120 × 0.8) 20.8 A
240 V Single-phase 10 kW 10,000 ÷ (240 × 0.8) 52.1 A
208 V Three-phase 50 kW 50,000 ÷ (1.732 × 208 × 0.8) 173.5 A
480 V Three-phase 500 kW 500,000 ÷ (1.732 × 480 × 0.8) 751.8 A
400 V Three-phase 500 kW 500,000 ÷ (1.732 × 400 × 0.8) 902.1 A
415 V Three-phase 250 kW 250,000 ÷ (1.732 × 415 × 0.8) 434.8 A
48 V DC 12 kW 12,000 ÷ 48 250 A

Cross-check any three-phase result through apparent power. For the 500 kW load at 400 V, kVA = 500 ÷ 0.8 = 625 kVA, and 625,000 ÷ (1.732 × 400) = 902 A. If the two routes disagree, the power factor has been applied twice or not at all.

Notice what voltage does. The same 500 kW load draws about 752 A at 480 V but about 902 A at 400 V. A higher voltage means less current, which is why larger plants move to medium voltage.

Generator Sizing Chart: kW, kVA and Amps at 480 V and 400 V

The chart converts common generator ratings into full-load line current. It assumes a 0.8 power factor, three-phase output, 60 Hz at 480 V and 50 Hz at 400 V. You can also check our generator sizing chart for 380 V, 400 V and 415 V.

Generator rating (kW, 0.8 PF) kVA Amps at 480 V, 3-phase, 60 Hz Amps at 400 V, 3-phase, 50 Hz
20 25 30 36
30 37.5 45 54
50 62.5 75 90
75 93.8 113 135
100 125 150 180
150 187.5 226 271
200 250 301 361
250 312.5 376 451
300 375 451 541
400 500 601 722
500 625 752 902
600 750 902 1,083
750 937.5 1,128 1,353
800 1,000 1,203 1,443
1,000 1,250 1,504 1,804
1,250 1,562.5 1,879 2,255
1,500 1,875 2,255 2,706
1,750 2,187.5 2,631 3,157
2,000 2,500 3,007 3,608

Figures are calculated and rounded to the nearest amp. They are rated full-load currents at the stated ratings, not site-derated values.

How to read the chart

  1. Start with the generator rating in kW.
  2. Read across to the kVA rating. kVA is what the alternator and cabling must carry. It is kW divided by 0.8.
  3. Pick the voltage column that matches your system, 480 V or 400 V.
  4. Use the amps figure as the starting point for breaker, cable and busbar selection.

As a quick check, a 1,000 kW generator is a 1,250 kVA machine. It delivers about 1,504 A at 480 V and about 1,804 A at 400 V.

Common kW to Amps Mistakes

  • Using line-to-neutral voltage in the three-phase formula. On a 400/230 V system use 400, not 230.
  • Applying power factor to a kVA figure. kVA already includes it.
  • Assuming a power factor of 1.0 for motor loads. That understates current and undersizes the supply.
  • Mixing 1.73 and 1.732. Pick one value and use it throughout the sheet.
  • Treating rated current as the design current. Altitude, temperature, motor starting and harmonics all change what the system must carry.

kW to Amps Calculator

Enter the load in kW, choose the phase and voltage, and set the power factor. The result updates as you type. It uses the formulas above.

kW to Amps Calculator

Current: 902 A

First-pass figure at rated load. Size cables and protection to the applicable code and the equipment datasheet.

Sizing Generators for the Current You Calculated

Once you know the amps, match them to a machine. USP&E lists new, new surplus and used diesel generators in 50 Hz and 60 Hz, alongside 1 MW to 4 MW generators for larger site loads. Behind the listings is an EPC and O&M contractor with 150+ power projects in 45+ countries, 25,000 MW contracted since 2002, and 24+ years of delivery.

Browse the diesel generators in the USP&E inventory and send a quote request with your kW, voltage, frequency and site conditions. Inventory is subject to prior sale.

kW to Amps FAQ

How do I convert kW to amps?

Multiply kW by 1,000, then divide by the voltage times the power factor. For three-phase, also multiply the divisor by √3 (1.732) and use line-to-line voltage. Single-phase: I = kW × 1,000 ÷ (V × PF). Three-phase: I = kW × 1,000 ÷ (√3 × V × PF). For DC, I = kW × 1,000 ÷ V.

How many amps is 100 kW?

It depends on voltage and phase. At 0.8 power factor, 100 kW draws about 150 A on a 480 V three-phase supply, about 180 A at 400 V three-phase, and about 347 A at 208 V three-phase. On a single-phase 240 V supply it draws about 521 A.

How many amps is 1 MW at 480 V?

A 1 MW (1,000 kW) load at 0.8 power factor on a 480 V three-phase supply draws about 1,504 A. The same load at 400 V draws about 1,804 A. The equivalent apparent power is 1,250 kVA.

What power factor should I use to convert kW to amps?

Use the power factor on the equipment nameplate or datasheet. Generator sets are normally rated at 0.8, so 0.8 is the usual figure for generator sizing. Resistive loads such as heaters are close to 1.0. A lower power factor means more amps for the same kW.

How do I convert kVA to amps?

Divide kVA by the voltage and multiply by 1,000. For three-phase, also divide by √3. No power factor term is needed because kVA already includes it. For example, 625 kVA at 400 V three-phase is 625,000 ÷ (1.732 × 400) = 902 A.

What is the difference between kW and kVA?

kW is real power, the useful work the load performs. kVA is apparent power, the total the generator, cables and switchgear must carry. They are linked by power factor: kW = kVA × PF. At a 0.8 power factor, a 1,000 kVA generator delivers 800 kW.

Which voltage do I use in the three-phase formula?

Use the line-to-line voltage. On a 400/230 V system that is 400 V, not 230 V. On a 480/277 V system it is 480 V, not 277 V. Using the line-to-neutral value overstates the current by about 73 percent.

Does the kW to amps formula change for DC?

Yes. DC has no power factor and no phase, so amps equal watts divided by volts: I = kW × 1,000 ÷ V. For example, 12 kW at 48 V DC draws 250 A.

Can I size a generator breaker or cable from this table alone?

No. The table gives rated full-load current. Breaker and cable sizing must follow the applicable electrical code, derating, motor-starting current and the equipment datasheet. Have a qualified engineer confirm the design before you specify protection.