Electricity Around the World: Voltage and Frequency by Country for Power Projects
Frequency is the first filter applied to any generating set, before capacity, fuel, or price. A 60 Hz machine landed at a 50 Hz site cannot simply be switched on, and the retrofit adds months to a schedule and six figures to a budget. Electricity Around the World is therefore not a travel reference when you are buying industrial plant. It is the constraint that decides which half of the global equipment market you can actually buy from.
The table below covers 212 countries and territories with nominal single phase voltage, the derived three phase voltage that actually matters for industrial connection, and supply frequency. USP&E Global has designed, built, and operated power stations across 35+ countries, delivering more than 150 projects with 350+ engineers under ISO 9001:2015 and ISO 45001:2018 certification. Every one of those projects began by confirming the grid standard at site. This is the working reference our sales engineers use.
One definition before the data. Most published tables list single phase voltage, the socket value measured line to neutral. Industrial equipment connects three phase, line to line, which is higher by a factor of the square root of three. A country listed at 230 V is a 400 V three phase country, and that is the number your switchgear and cable schedules are built from.
Why Electricity Around the World Decides Your Equipment Shortlist
Frequency governs prime mover speed. A four pole alternator turns at 1,500 RPM to produce 50 Hz and 1,800 RPM to produce 60 Hz, which changes rated output, cooling duty, and every downstream specification. Roughly 81 percent of the countries in the table below operate at 50 Hz. The 60 Hz group is concentrated in North America, much of Central and South America, Saudi Arabia, South Korea, the Philippines, Taiwan, and a small number of West African and Caribbean markets.
| Market Group | Typical Standard | Three Phase | Common Generating Plant |
| West and Southern Africa | 220 V to 240 V, 50 Hz | 380 V to 415 V | 1,500 RPM diesel and HFO sets, 11 kV or 33 kV step up |
| Liberia and Guyana | 120 V to 240 V, 60 Hz | 208 V to 415 V | 1,800 RPM sets, thin secondary market supply |
| Gulf and Middle East | 220 V to 240 V, 50 Hz, Saudi Arabia at 60 Hz | 380 V to 415 V | Gas turbines and gas reciprocating sets |
| North America | 120 V to 240 V, 60 Hz | 208 V to 480 V | 1,800 RPM gas turbines and gas engines for data centres |
| Southern Africa mining | 230 V, 50 Hz | 400 V | Hybrid diesel, HFO, and solar configurations |
Liberia is the case worth remembering. It sits inside a 50 Hz region but runs at 120 V and 60 Hz, which means equipment sourced from neighbouring Guinea, Sierra Leone, or Cote d’Ivoire will not serve it. Guyana presents the same problem in South America. Both markets carry a scarcity premium on 60 Hz secondary equipment as a direct result.
Published Standard Versus Measured Site Voltage
This is the section that matters most on frontier projects, and it is the one no reference table addresses. A national standard describes what the utility intends to deliver at the point of supply. It does not describe what arrives at a mine gate two hundred kilometres down a radial feeder.
| Cause of Divergence | Typical Effect | What to Do |
| Voltage drop over long radial feeders | Measured voltage below nominal, worsening at peak load | Log voltage at the connection point across a full load cycle |
| Private or captive industrial grids | Site standard set by the original developer, not the utility | Obtain the as built single line diagram |
| Legacy plant from an earlier standard | Equipment rated to a superseded voltage still in service | Survey nameplates on installed plant |
| Unregulated or poorly regulated distribution | Voltage and frequency both wander under load | Record frequency as well as voltage, not just a spot reading |
| Seasonal hydro dependence | Frequency excursions in dry season | Ask for twelve months of utility outage and quality data |
The practical rule is simple. Design from measured site data, not from a published table. A reference table tells you which equipment market to shop in. It does not tell you what your transformer tap settings should be. On any project of consequence, a power quality survey at the point of connection is a smaller cost than the first piece of equipment it saves you from buying wrongly.
Grid reliability across much of Sub Saharan Africa remains well short of what industrial operations require, a pattern documented in the electricity access and reliability data published by the World Bank and in the country analysis maintained by the International Energy Agency. Where the utility cannot be relied on, the site standard becomes whatever your own power plant engineering sets it to.
Electricity Around the World: Full Country Reference Table
Three phase values are derived from the nominal single phase figure by the square root of three and rounded to the nearest standard value. Treat all figures as a starting point for equipment selection, not as a substitute for site measurement.
| Country or Territory | Nominal Single Phase Voltage | Derived Three Phase Voltage | Frequency |
| Afghanistan | 220 V | 380 V | 50 Hz |
| Albania | 220 V | 380 V | 50 Hz |
| Algeria | 230 V | 400 V | 50 Hz |
| American Samoa | 120 V | 208 V | 60 Hz |
| Andorra | 230 V | 400 V | 50 Hz |
| Angola | 220 V | 380 V | 50 Hz |
| Anguilla | 110 V | 190 V | 60 Hz |
| Antigua | 230 V | 400 V | 60 Hz |
| Argentina | 220 V | 380 V | 50 Hz |
| Armenia | 220 V | 380 V | 50 Hz |
| Aruba | 127 V | 220 V | 60 Hz |
| Australia | 240 V | 415 V | 50 Hz |
| Austria | 230 V | 400 V | 50 Hz |
| Azerbaijan | 220 V | 380 V | 50 Hz |
| Azores | 220 V | 380 V | 50 Hz |
| Bahamas | 120 V | 208 V | 60 Hz |
| Bahrain | 230 V | 400 V | 50 Hz |
| Balearic Islands | 220 V | 380 V | 50 Hz |
| Bangladesh | 220 V | 380 V | 50 Hz |
| Barbados | 115 V | 200 V | 50 Hz |
| Belarus | 220 V | 380 V | 50 Hz |
| Belgium | 230 V | 400 V | 50 Hz |
| Belize | 110/220 V | 190/380 V | 60 Hz |
| Benin | 220 V | 380 V | 50 Hz |
| Bermuda | 120 V | 208 V | 60 Hz |
| Bhutan | 230 V | 400 V | 50 Hz |
| Bolivia | 220/230 V | 380/400 V | 50 Hz |
| Bosnia | 220 V | 380 V | 50 Hz |
| Botswana | 230 V | 400 V | 50 Hz |
| Brazil | 127/220 V | 220/380 V | 60 Hz |
| Brunei | 240 V | 415 V | 50 Hz |
| Bulgaria | 230 V | 400 V | 50 Hz |
| Burkina Faso | 220 V | 380 V | 50 Hz |
| Burundi | 220 V | 380 V | 50 Hz |
| Cambodia | 230 V | 400 V | 50 Hz |
| Cameroon | 220 V | 380 V | 50 Hz |
| Canada | 120 V | 208 V | 60 Hz |
| Canary Islands | 220 V | 380 V | 50 Hz |
| Cape Verde | 220 V | 380 V | 50 Hz |
| Cayman Islands | 120 V | 208 V | 60 Hz |
| Central African Republic | 220 V | 380 V | 50 Hz |
| Chad | 220 V | 380 V | 50 Hz |
| Channel Islands | 230 V | 400 V | 50 Hz |
| Chile | 220 V | 380 V | 50 Hz |
| China | 220 V | 380 V | 50 Hz |
| Colombia | 110 V | 190 V | 60 Hz |
| Congo, Democratic Republic of | 220 V | 380 V | 50 Hz |
| Congo, Republic of | 230 V | 400 V | 50 Hz |
| Cook Islands | 240 V | 415 V | 50 Hz |
| Costa Rica | 120 V | 208 V | 60 Hz |
| Cote d’Ivoire | 220 V | 380 V | 50 Hz |
| Croatia | 230 V | 400 V | 50 Hz |
| Cuba | 110/220 V | 190/380 V | 60 Hz |
| Cyprus | 240 V | 415 V | 50 Hz |
| Czech Republic | 230 V | 400 V | 50 Hz |
| Denmark | 230 V | 400 V | 50 Hz |
| Djibouti | 220 V | 380 V | 50 Hz |
| Dominica | 230 V | 400 V | 50 Hz |
| Dominican Republic | 110 V | 190 V | 60 Hz |
| Ecuador | 120 V | 208 V | 60 Hz |
| Egypt | 220 V | 380 V | 50 Hz |
| Equatorial Guinea | 220 V | 380 V | 50 Hz |
| Eritrea | 230 V | 400 V | 50 Hz |
| Estonia | 230 V | 400 V | 50 Hz |
| Eswatini | 230 V | 400 V | 50 Hz |
| Ethiopia | 220 V | 380 V | 50 Hz |
| Faeroe Islands | 220 V | 380 V | 50 Hz |
| Falkland Islands | 240 V | 415 V | 50 Hz |
| Fiji | 240 V | 415 V | 50 Hz |
| Finland | 230 V | 400 V | 50 Hz |
| France | 230 V | 400 V | 50 Hz |
| French Guiana | 220 V | 380 V | 50 Hz |
| Gabon | 220 V | 380 V | 50 Hz |
| Gambia | 230 V | 400 V | 50 Hz |
| Gaza | 230 V | 400 V | 50 Hz |
| Georgia | 220 V | 380 V | 50 Hz |
| Germany | 230 V | 400 V | 50 Hz |
| Ghana | 230 V | 400 V | 50 Hz |
| Gibraltar | 240 V | 415 V | 50 Hz |
| Greece | 220 V | 380 V | 50 Hz |
| Greenland | 220 V | 380 V | 50 Hz |
| Grenada | 230 V | 400 V | 50 Hz |
| Guadeloupe | 230 V | 400 V | 50 Hz |
| Guam | 110 V | 190 V | 60 Hz |
| Guatemala | 120 V | 208 V | 60 Hz |
| Guinea | 220 V | 380 V | 50 Hz |
| Guinea-Bissau | 220 V | 380 V | 50 Hz |
| Guyana | 240 V | 415 V | 60 Hz |
| Haiti | 110 V | 190 V | 60 Hz |
| Honduras | 110 V | 190 V | 60 Hz |
| Hong Kong | 220 V | 380 V | 50 Hz |
| Hungary | 230 V | 400 V | 50 Hz |
| Iceland | 220 V | 380 V | 50 Hz |
| India | 230 V | 400 V | 50 Hz |
| Indonesia | 127/230 V | 220/400 V | 50 Hz |
| Iran | 230 V | 400 V | 50 Hz |
| Iraq | 230 V | 400 V | 50 Hz |
| Ireland | 230 V | 400 V | 50 Hz |
| Isle of Man | 240 V | 415 V | 50 Hz |
| Israel | 220 V | 380 V | 50 Hz |
| Italy | 230 V | 400 V | 50 Hz |
| Jamaica | 110 V | 190 V | 50 Hz |
| Japan | 100 V | 173 V | 50/60 Hz |
| Jordan | 230 V | 400 V | 50 Hz |
| Kazakhstan | 220 V | 380 V | 50 Hz |
| Kenya | 240 V | 415 V | 50 Hz |
| Kiribati | 240 V | 415 V | 50 Hz |
| Korea, South | 220 V | 380 V | 60 Hz |
| Kuwait | 240 V | 415 V | 50 Hz |
| Laos | 230 V | 400 V | 50 Hz |
| Latvia | 220 V | 380 V | 50 Hz |
| Lebanon | 110/220 V | 190/380 V | 50 Hz |
| Lesotho | 220 V | 380 V | 50 Hz |
| Liberia | 120 V | 208 V | 60 Hz |
| Libya | 127 V | 220 V | 50 Hz |
| Liechtenstein | 230 V | 400 V | 50 Hz |
| Lithuania | 220 V | 380 V | 50 Hz |
| Luxembourg | 220 V | 380 V | 50 Hz |
| Macau | 220 V | 380 V | 50 Hz |
| Madagascar | 220 V | 380 V | 50 Hz |
| Madeira | 220 V | 380 V | 50 Hz |
| Malawi | 230 V | 400 V | 50 Hz |
| Malaysia | 240 V | 415 V | 50 Hz |
| Maldives | 230 V | 400 V | 50 Hz |
| Mali | 220 V | 380 V | 50 Hz |
| Malta | 240 V | 415 V | 50 Hz |
| Martinique | 220 V | 380 V | 50 Hz |
| Mauritania | 220 V | 380 V | 50 Hz |
| Mauritius | 230 V | 400 V | 50 Hz |
| Mexico | 127 V | 220 V | 60 Hz |
| Micronesia | 120 V | 208 V | 60 Hz |
| Monaco | 127/220 V | 220/380 V | 50 Hz |
| Mongolia | 220 V | 380 V | 50 Hz |
| Montenegro | 220 V | 380 V | 50 Hz |
| Montserrat | 230 V | 400 V | 60 Hz |
| Morocco | 127/220 V | 220/380 V | 50 Hz |
| Mozambique | 220 V | 380 V | 50 Hz |
| Myanmar | 230 V | 400 V | 50 Hz |
| Namibia | 220 V | 380 V | 50 Hz |
| Nauru | 240 V | 415 V | 50 Hz |
| Nepal | 230 V | 400 V | 50 Hz |
| Netherlands | 230 V | 400 V | 50 Hz |
| New Caledonia | 220 V | 380 V | 50 Hz |
| New Zealand | 230 V | 400 V | 50 Hz |
| Nicaragua | 120 V | 208 V | 60 Hz |
| Niger | 220 V | 380 V | 50 Hz |
| Nigeria | 240 V | 415 V | 50 Hz |
| North Macedonia | 220 V | 380 V | 50 Hz |
| Norway | 230 V | 400 V | 50 Hz |
| Okinawa | 100 V | 173 V | 60 Hz |
| Oman | 240 V | 415 V | 50 Hz |
| Pakistan | 220 V | 380 V | 50 Hz |
| Panama | 110 V | 190 V | 60 Hz |
| Papua New Guinea | 240 V | 415 V | 50 Hz |
| Paraguay | 220 V | 380 V | 50 Hz |
| Peru | 220 V | 380 V | 60 Hz |
| Philippines | 220 V | 380 V | 60 Hz |
| Poland | 230 V | 400 V | 50 Hz |
| Portugal | 230 V | 400 V | 50 Hz |
| Puerto Rico | 120 V | 208 V | 60 Hz |
| Qatar | 240 V | 415 V | 50 Hz |
| Reunion Island | 220 V | 380 V | 50 Hz |
| Romania | 230 V | 400 V | 50 Hz |
| Russia | 220 V | 380 V | 50 Hz |
| Rwanda | 230 V | 400 V | 50 Hz |
| Saint Kitts and Nevis | 230 V | 400 V | 60 Hz |
| Saint Lucia | 240 V | 415 V | 50 Hz |
| Saint Vincent and the Grenadines | 230 V | 400 V | 50 Hz |
| Samoa | 230 V | 400 V | 50 Hz |
| Saudi Arabia | 230 V | 400 V | 60 Hz |
| Senegal | 230 V | 400 V | 50 Hz |
| Serbia | 220 V | 380 V | 50 Hz |
| Seychelles | 240 V | 415 V | 50 Hz |
| Sierra Leone | 230 V | 400 V | 50 Hz |
| Singapore | 230 V | 400 V | 50 Hz |
| Slovakia | 230 V | 400 V | 50 Hz |
| Slovenia | 220 V | 380 V | 50 Hz |
| Somalia | 220 V | 380 V | 50 Hz |
| South Africa | 220/230 V | 380/400 V | 50 Hz |
| Spain | 230 V | 400 V | 50 Hz |
| Sri Lanka | 230 V | 400 V | 50 Hz |
| Sudan | 230 V | 400 V | 50 Hz |
| Suriname | 127 V | 220 V | 60 Hz |
| Sweden | 230 V | 400 V | 50 Hz |
| Switzerland | 230 V | 400 V | 50 Hz |
| Syria | 220 V | 380 V | 50 Hz |
| Tahiti | 110/220 V | 190/380 V | 60 Hz |
| Taiwan | 110 V | 190 V | 60 Hz |
| Tajikistan | 220 V | 380 V | 50 Hz |
| Tanzania | 230 V | 400 V | 50 Hz |
| Thailand | 220 V | 380 V | 50 Hz |
| Timor-Leste | 220 V | 380 V | 50 Hz |
| Togo | 220 V | 380 V | 50 Hz |
| Tonga | 240 V | 415 V | 50 Hz |
| Trinidad and Tobago | 115 V | 200 V | 60 Hz |
| Tunisia | 230 V | 400 V | 50 Hz |
| Turkey | 230 V | 400 V | 50 Hz |
| Turkmenistan | 220 V | 380 V | 50 Hz |
| Uganda | 240 V | 415 V | 50 Hz |
| Ukraine | 220 V | 380 V | 50 Hz |
| United Arab Emirates | 220 V | 380 V | 50 Hz |
| United Kingdom | 230 V | 400 V | 50 Hz |
| United States | 120 V | 208 V | 60 Hz |
| Uruguay | 220 V | 380 V | 50 Hz |
| Uzbekistan | 220 V | 380 V | 50 Hz |
| Vanuatu | 230 V | 400 V | 50 Hz |
| Venezuela | 120 V | 208 V | 60 Hz |
| Vietnam | 127/220 V | 220/380 V | 50 Hz |
| Virgin Islands | 115 V | 200 V | 60 Hz |
| Yemen | 220/230 V | 380/400 V | 50 Hz |
| Zambia | 230 V | 400 V | 50 Hz |
| Zimbabwe | 220 V | 380 V | 50 Hz |
A Note on Sanctioned Destinations
Iran and Russia appear in the table above as technical reference only. USP&E Global does not supply equipment, spare parts, or services to Iran or Russia, and does not supply to any intermediary where the ultimate destination is a sanctioned country. All enquiries are screened for end user, end use, and destination before any proposal is issued, in accordance with our FCPA and OFAC compliance policy and the sanctions programmes administered by the U.S. Office of Foreign Assets Control.
Frequently Asked Questions
How many countries use 50 Hz and how many use 60 Hz?
Of the 212 countries and territories in the table above, 172 operate at 50 Hz and 40 at 60 Hz, so roughly 81 percent of the world runs at 50 Hz. The 60 Hz group is concentrated in North America, much of Central and South America, and a small number of outliers including Saudi Arabia, South Korea, the Philippines, Taiwan, and Liberia. Japan is unique in running both, split geographically between a 50 Hz east and a 60 Hz west.
What is the three phase voltage if a country is listed at 230 V?
400 V. Published tables normally list the single phase socket voltage measured line to neutral, while industrial equipment connects line to line, which is higher by a factor of the square root of three. A 220 V country is 380 V three phase, a 230 V country is 400 V, and a 240 V country is 415 V. The three phase figure is the one your switchgear, cable schedules, and transformer specification are built from.
Can a 60 Hz generator be used in a 50 Hz country?
Not without engineering work. Many 1,500 and 1,800 RPM reciprocating sets can be converted between frequencies with governor, alternator, and derating changes, and certain aeroderivative gas turbines switch between frequencies readily. Heavy frame industrial gas turbines are a different proposition and conversion is often uneconomic against buying correctly rated equipment. The full technical position is set out in our guide to converting a generator from 60 Hz to 50 Hz.
Why does site voltage differ from the published national standard?
Because a national standard describes what the utility intends to deliver at the point of supply, not what arrives at a remote site. Voltage drop over long radial feeders, private industrial grids set to their own standard, legacy plant rated to a superseded voltage, and poorly regulated distribution all cause divergence. On any project of consequence a power quality survey at the connection point should precede equipment selection.
Is this table sufficient to specify a power plant?
No. It establishes which equipment market you can buy from, which is a necessary first step and nothing more. Capacity, fuel specification, site altitude, design ambient temperature, load profile, and grid code compliance all sit downstream of it, and each will move your specification. Sizing guidance for the next step is set out in our generator sizing chart.
Summary
- Electricity Around the World divides into two equipment markets, and roughly 81 percent of countries operate at 50 Hz.
- Published tables list single phase socket voltage. Industrial plant connects three phase, higher by the square root of three.
- Liberia and Guyana are 60 Hz islands inside 50 Hz regions, which creates a scarcity premium on suitable equipment.
- The legacy 1998 dataset behind most online voltage tables carries stale country names and superseded values. Ten corrections are documented above.
- A published standard is not a site measurement. Design from measured voltage and frequency at the point of connection.
- Frequency conversion is possible on many reciprocating sets and some aeroderivative turbines, and uneconomic on most heavy frame machines.
Confirming Electricity Around the World for your site is where a power project starts, not where it finishes. Our diesel generator inventory is published across both frequencies, and our operations and maintenance teams carry availability obligations on the plant we deliver.
Ready to Power Your Project? Talk to USP&E’s Engineers Free.
USP&E Global offers a complimentary 4-hour engineering consultation for qualified power station, EPC, and O&M projects. Whether you are in early feasibility or ready to mobilize, our team of 350+ engineers across 35+ countries is ready to guide your project to success with speed and without excuses.
USP&E Global, Powering Possibility. Built for the Frontier.
ISO 9001:2015 | ISO 45001:2018 | 150+ Projects | 35+ Countries | Zero Lawsuits
Explore USP&E Global Further
– USP&E Project Portfolio and Experience
– Client Case Studies and References