Dry Low NOx Gas Turbines: How DLN Combustion and SCR Shape Your Permit
Dry low NOx combustion is one of the first things an air permit engineer asks about when a gas turbine project is proposed. Nitrogen oxides, or NOx, are among the main pollutants from burning natural gas, and limits on them shape equipment choice, plant layout and operating cost. For developers, utilities, data centre operators and industrial users, understanding dry low NOx technology early can prevent a late and expensive redesign.
This guide explains how dry low NOx combustion works, what an emissions figure such as 25 ppmv at 15% O2 means, when selective catalytic reduction is needed on top, and how these choices affect cost and schedule. It uses the FX-45, a new-build 45 MW gas turbine generator package from USP&E with dry low NOx combustion, as a worked example. Every FX-45 figure here comes from the published FX-45 product page.
USP&E has delivered 150+ power projects in 45+ countries since 2002, with 25,000 MW contracted since 2002. USP&E holds ISO 9001:2015 and ISO 45001:2018 certification and works across equipment supply, EPC (Engineering, Procurement and Construction) and O&M (Operations and Maintenance).
For the full equipment scope, read the guide to what a gas turbine generator package includes. For onsite supply, see the guide to behind the meter natural gas turbine generators, and for higher efficiency, read how to build combined cycle power plants in phases. For a wider view of permits, USP&E also covers emissions compliance for natural gas turbines.
What Is Dry Low NOx? Specifications and Ratings
Dry low NOx, often shortened to DLN or DLE (dry low emissions), is a combustion design that limits NOx formation without injecting water or steam. Most NOx in a gas turbine forms when nitrogen and oxygen in the air react at very high flame temperatures. Dry low NOx combustors premix fuel and air before they burn, so the mixture burns leaner and cooler, and less NOx forms.
The word “dry” separates this approach from older wet methods, which injected water or steam into the combustor to cool the flame. Wet methods need a supply of treated water and can affect efficiency and maintenance. DLN combustion avoids that water demand, which matters at desert and remote sites.
NOx itself is a health and environmental concern. The U.S. Environmental Protection Agency explains the effects in its basic information about NO2, and lists nitrogen dioxide among the criteria air pollutants it regulates.
FX-45 emissions and ratings
|
Dry low NOx parameter |
FX-45 published value |
What it means |
|
Combustion system |
Dry low NOx (dry low emissions) |
No water or steam injection for NOx control |
|
NOx emissions |
25 ppmv at 15% O2 |
Concentration corrected to a reference oxygen level |
|
Lower NOx option |
SCR under a separate agreement |
For permits that need single-digit NOx |
|
Primary fuel |
Natural gas |
Gas quality affects combustion |
|
Rated output |
45 MW at ISO conditions |
Block size before site derating |
|
Major inspection |
48,000 equivalent operating hours |
Includes combustion system maintenance planning |
Source: USP&E FX-45 page. Performance figures at ISO conditions: 15 degrees Celsius, sea level, 60% relative humidity, natural gas, new and clean, at the generator terminals and a power factor of 0.8.
Part load and fuel quality
Low NOx performance is usually stated over a defined load range. At low loads, lean premixed combustion can become less stable, so many combustors change mode and NOx can rise. Ask each supplier over what load range its NOx figure applies, and how the unit behaves during start-up and shutdown.
Fuel quality matters too. Lean premixed flames are sensitive to gas composition, heating value and contaminants. That is why USP&E asks for a gas analysis with every enquiry, and why fuel gas conditioning is part of the FX-45 scope of supply.
What 25 ppmv at 15% O2 means
The figure 25 ppmv means 25 parts per million by volume of NOx in the exhaust. The phrase “at 15% O2” means the figure is corrected to a standard oxygen content of 15%. Gas turbines run with a lot of excess air, so correcting to a fixed oxygen level lets regulators compare machines fairly. Always check that offers state NOx at the same reference oxygen level, or the numbers will not be comparable.
Dry Low NOx Cost: Price and Total Installed Cost
DLN combustion is part of the FX-45 package, so it does not appear as a separate line item. FX-45 pricing is issued under a non-disclosure agreement in a site-specific quotation, so no FX-45 price is quoted here.
Selective catalytic reduction is different. SCR is a post-combustion system that injects a reagent, usually ammonia or urea, into the exhaust ahead of a catalyst, which converts NOx into nitrogen and water. On the FX-45, SCR is available under a separate agreement and is never included in the package price. It adds equipment, reagent supply, space and maintenance.
Third-party references help you test a budget. The U.S. Energy Information Administration’s Assumptions to the Annual Energy Outlook 2026 (April 2026) puts the total overnight cost of a new industrial frame simple cycle plant at about $1,158 per kW in 2025 US dollars. The Sargent & Lundy reference case for the EIA (January 2024) groups gas turbines and emissions catalysts together as major equipment, at about 46% of total capital cost, calculated by USP&E and indicative only.
Dry low NOx compared with SCR and wet injection
|
NOx control method |
How it works |
Main trade-off |
|
Dry low NOx combustion |
Lean premixed combustion lowers flame temperature |
No water needed; built into the combustor |
|
Water or steam injection |
Cools the flame with water or steam |
Needs treated water and adds maintenance |
|
Selective catalytic reduction |
Catalyst and reagent remove NOx from exhaust |
Lowest NOx, with added cost, space and reagent |
|
Dry low NOx plus SCR |
Combustor limits NOx, SCR removes more |
Used where permits need single-digit NOx |
Source: FX-45 values from the USP&E FX-45 page. Method descriptions are general engineering practice.
New vs Used Gas Turbines: Dry Low NOx, Inspection and Warranty
Emissions performance is a key difference between new and used units. A new-build package is designed to a current combustion standard and comes with documentation and a warranty. A used unit may have an older combustor, wet injection or modified hardware, and its emissions history must be checked.
The Electric Power Research Institute (EPRI) reported in Utility Dive in March 2026 that large new gas turbines take more than five years from order, and smaller units 18 to 36 months. USP&E states that the FX-45 is delivered in 18 to 24 months from slot reservation, with first deliveries from 2028.
New-build dry low NOx package compared with used units
|
Factor |
New-build FX-45 package |
Used gas turbine |
|
Combustion system |
DLN |
Varies; may be older or wet |
|
NOx performance |
25 ppmv at 15% O2 |
Must be verified by test |
|
Warranty |
New-build with warranty |
Usually limited or none |
|
Documentation |
One document set on every unit |
Must be verified |
|
Delivery |
18 to 24 months from slot reservation |
Months, if already built |
Source: USP&E FX-45 page for FX-45 values. Used unit factors are general practice.
If you consider used equipment, ask for recent emissions test results and confirm the combustor type. You can browse current inventory of gas turbines for sale and request records for any unit before you shortlist it.
Fuel Type Comparison
NOx control varies by fuel and technology. Figures are indicative third-party references, not USP&E prices.
|
Fuel Type |
CapEx Range |
OpEx Range |
Typical Lead Time |
Best Application |
|
Natural gas, industrial frame simple cycle |
About $1,158/kW (EIA 2026) |
About $7.18/kW per year plus $4.17/MWh (EIA 2026) |
More than five years for large new units (EPRI 2026); FX-45 18 to 24 months from slot reservation |
Base load and peaking blocks |
|
Natural gas, aeroderivative simple cycle |
About $2,275/kW (EIA 2026) |
About $9.99/kW per year plus $5.97/MWh (EIA 2026) |
18 to 36 months for smaller new units (EPRI 2026) |
Fast start and peaking |
|
Natural gas, combined cycle |
About $1,032 to $1,086/kW (EIA 2026) |
About $12.69 to $16.23/kW per year plus about $3.5/MWh (EIA 2026) |
About 40 to 42 months from development start (Sargent & Lundy for EIA, 2024) |
Efficient base load |
|
Diesel, containerised gensets |
About $650 to $880/kW installed (NREL REopt defaults) |
About $10 to $20/kW per year fixed, plus fuel (NREL REopt defaults) |
Often under 90 to 120 days, site dependent |
Standby and short-term supply |
|
HFO (Heavy Fuel Oil), engine power station |
About $800 to $1,000/kW, medium speed engines (IDB Invest, 2010 US dollars) |
Typically 9 to 14 months from deposit |
Remote base load without gas |
Sources: EIA, Assumptions to the Annual Energy Outlook 2026, Table 3 (2025 US dollars); EPRI in Utility Dive (2026); Sargent & Lundy for EIA (2024). Diesel: NREL REopt model default values (REopt generator defaults, checked 2026). HFO: IDB Invest, Liquid and Gaseous Fossil Fuel Power Plant Guidelines, citing 2010 cost data. CapEx means capital expenditure and OpEx means operating expenditure. Blank cells could not be verified from a credible public source.
In the United States, the U.S. Environmental Protection Agency sets Clean Air Act standards for engines and combustion turbines. Other countries set their own limits, and lenders may apply their own guidelines. The EIA explains the basics of how electricity is generated for readers new to the technology.
Dry Low NOx and Your Air Permit: From Enquiry to Operation
Dry low NOx decisions are easier when they follow the permit process. The steps below show a typical sequence.
Step 1: Identify the applicable limits
Find out which NOx limits apply at your site, and the reference oxygen level they use. Ask whether lenders apply extra standards.
Step 2: Compare limits with dry low NOx performance
Compare the limit with the package figure. The FX-45 DLN combustor holds NOx to 25 ppmv at 15% O2. If the limit is higher, dry low NOx alone may be enough.
Step 3: Decide whether SCR is needed
If the permit needs single-digit NOx, plan for selective catalytic reduction. On the FX-45, SCR is available under a separate agreement.
Step 4: Send a gas analysis
Gas composition affects combustion stability and emissions. USP&E asks for a gas analysis with every enquiry, along with site location, frequency and voltage, and when you need power on.
Step 5: Prepare the air permit application
The air permit application usually needs emissions data, stack details and operating hours. Start it early, because reviews can take time.
Step 6: Commission and test emissions
Emissions testing at commissioning confirms performance. Agree the test method and acceptance criteria in the contract.
Step 7: Maintain combustion performance
Combustion systems need tuning and inspection over time. Plan maintenance through an LTSA. USP&E offers LTSA and O&M alongside the equipment, contracted separately.
Common dry low NOx mistakes to avoid
- Comparing NOx figures at different oxygen levels. Always check the reference oxygen level.
- Assuming dry low NOx meets every permit. Some limits need SCR.
- Ignoring gas quality. Gas composition affects combustion and emissions.
- Leaving permits late. Permit reviews can set the critical path.
- Forgetting SCR space. If SCR may be needed later, reserve space in the layout.
Case Studies: Dry Low NOx in Real Projects
First FX-45 deliveries are stated from 2028, so no FX-45 project results exist yet. USP&E only publishes approved case studies.
A typical dry low NOx project starts with the site permit limits and a gas analysis. The FX-45 DLN combustor sets the baseline at 25 ppmv at 15% O2, and the team decides early whether SCR is needed, reserving space in the layout if it might be. USP&E supports permit-ready engineering with engineering, EPC and O&M teams that have delivered projects in 45+ countries.
The lessons below reflect common practice, not a specific project:
- Projects that check reference oxygen levels early avoid misreading offers.
- Projects that reserve SCR space avoid costly layout changes later.
- Projects that start permitting early avoid delays at commissioning.
How to Choose a Dry Low NOx Gas Turbine Supplier: 10 Criteria
Use these criteria to compare emissions performance across offers.
- Stated NOx level. Ask for NOx with the reference oxygen level.
- Combustion type. Confirm DLN or another method, and the combustor generation.
- Load range. Ask over what load range the NOx figure applies.
- SCR option. Ask whether SCR is included or separate.
- Gas flexibility. Confirm the gas quality range for stable combustion.
- Emissions warranty. Ask what emissions level is warranted and how it is tested.
- Maintenance plan. Ask how combustion tuning and inspection are handled.
- Delivery commitment. Ask for a written delivery window.
- EPC capability. A supplier that can build the plant can integrate SCR and stack design. USP&E supports this through its power plant EPC projects team.
- Compliance and certification. Look for ISO 9001 and ISO 45001 certification and a written sanctions and anti-corruption policy.
FAQ: Dry Low NOx
What does DLN mean on a gas turbine?
DLN stands for dry low NOx. It is a combustion design that premixes fuel and air before they burn, so the flame burns leaner and cooler. That reduces NOx formation without injecting water or steam into the combustor, which matters at dry sites.
What NOx does the FX-45 achieve?
The FX-45 dry low NOx combustor holds NOx to 25 ppmv at 15% O2, according to the USP&E FX-45 page. Compare that figure with your permit limit at the same reference oxygen level to see whether SCR is also needed.
When do I need SCR?
You need SCR where a permit requires single-digit NOx or a limit below what the combustor achieves. On the FX-45, SCR is available under a separate agreement and is not in the package price, so reserve space for it if it may be needed.
Why is NOx corrected to 15% oxygen?
NOx is corrected to 15% oxygen so that regulators and buyers can compare machines fairly. Gas turbines run with varying amounts of excess air, which dilutes the exhaust, so a fixed reference oxygen level removes that effect from every reported figure.
Does dry low NOx need water?
No. Dry low NOx combustion needs no water or steam for NOx control, which is what the word dry means. Older wet methods inject water or steam to cool the flame, which needs a supply of treated water and adds maintenance.
Can used turbines meet the same limits?
Used turbines can meet the same limits only if their combustor and condition allow it. Ask for recent emissions test results, confirm the combustor type and check whether any combustion hardware has been modified since the unit left the factory.
What does USP&E need to assess emissions?
USP&E needs site location, gas analysis, frequency and voltage, and when you need power on, plus your permit limits. With these, USP&E can compare the FX-45 baseline with your limits and advise whether SCR should be planned into the layout.
Key Takeaways: Dry Low NOx
- DLN combustion limits NOx without water or steam.
- The FX-45 holds NOx to 25 ppmv at 15% O2.
- Always compare NOx at the same reference oxygen level.
- Plan SCR where permits need single-digit NOx, and reserve space if it may be needed.
- Start the air permit early and send a gas analysis with every enquiry.
The right dry low NOx strategy matches your permit, your gas and your site. Send USP&E your site location, gas analysis, frequency, voltage, power date and permit limits, and its engineers will help you plan a dry low NOx gas turbine project that is ready for approval.