kW to kVA Conversion: The Full 0.8 Power Factor Table
A kW to kVA conversion is the first calculation in any generator sizing exercise, and the one most often skipped. kW is real power, the work the load actually performs. kVA is apparent power, the total the alternator, cabling, and switchgear must carry. Divide kW by the power factor to get kVA. At the industry standard 0.8 power factor the multiplier is 1.25, so a 800 kW load requires a 1,000 kVA machine. Specify on kW alone and the alternator is undersized by a quarter.
kW to kVA Conversion Table at 0.8 Power Factor
| Load (kW) | kW to kVA Conversion (kVA) | Load (kW) | kW to kVA Conversion (kVA) |
| 30 | 38 | 1,175 | 1,469 |
| 40 | 50 | 1,200 | 1,500 |
| 50 | 63 | 1,225 | 1,531 |
| 60 | 75 | 1,250 | 1,563 |
| 70 | 88 | 1,275 | 1,594 |
| 80 | 100 | 1,300 | 1,625 |
| 90 | 113 | 1,325 | 1,656 |
| 100 | 125 | 1,350 | 1,688 |
| 110 | 138 | 1,375 | 1,719 |
| 125 | 156 | 1,400 | 1,750 |
| 135 | 169 | 1,425 | 1,781 |
| 150 | 188 | 1,450 | 1,813 |
| 165 | 206 | 1,475 | 1,844 |
| 175 | 219 | 1,500 | 1,875 |
| 200 | 250 | 1,525 | 1,906 |
| 225 | 281 | 1,550 | 1,938 |
| 250 | 313 | 1,575 | 1,969 |
| 275 | 344 | 1,600 | 2,000 |
| 300 | 375 | 1,625 | 2,031 |
| 325 | 406 | 1,650 | 2,063 |
| 350 | 438 | 1,675 | 2,094 |
| 375 | 469 | 1,700 | 2,125 |
| 400 | 500 | 1,725 | 2,156 |
| 425 | 531 | 1,750 | 2,188 |
| 450 | 563 | 1,775 | 2,219 |
| 475 | 594 | 1,800 | 2,250 |
| 500 | 625 | 1,825 | 2,281 |
| 525 | 656 | 1,850 | 2,313 |
| 550 | 688 | 1,875 | 2,344 |
| 575 | 719 | 1,900 | 2,375 |
| 600 | 750 | 1,925 | 2,406 |
| 625 | 781 | 1,950 | 2,438 |
| 650 | 813 | 1,975 | 2,469 |
| 675 | 844 | 2,000 | 2,500 |
| 700 | 875 | 2,025 | 2,531 |
| 725 | 906 | 2,050 | 2,563 |
| 750 | 938 | 2,075 | 2,594 |
| 775 | 969 | 2,100 | 2,625 |
| 800 | 1,000 | 2,125 | 2,656 |
| 825 | 1,031 | 2,150 | 2,688 |
| 850 | 1,063 | 2,175 | 2,719 |
| 875 | 1,094 | 2,200 | 2,750 |
| 900 | 1,125 | 2,225 | 2,781 |
| 925 | 1,156 | 2,250 | 2,813 |
| 950 | 1,188 | 2,275 | 2,844 |
| 975 | 1,219 | 2,300 | 2,875 |
| 1,000 | 1,250 | 2,325 | 2,906 |
| 1,025 | 1,281 | 2,350 | 2,938 |
| 1,050 | 1,313 | 2,375 | 2,969 |
| 1,075 | 1,344 | 2,400 | 3,000 |
| 1,100 | 1,375 | 2,425 | 3,031 |
| 1,125 | 1,406 | 2,450 | 3,063 |
| 1,150 | 1,438 | 2,475 | 3,094 |
Values are rounded to the nearest kVA. Confirm whether the nameplate quotes a standby, prime, or continuous rating before sizing.
Why Power Factor Decides the Machine You Buy
Power factor is the ratio of real to apparent power, and it is set by the load, not the generator. Motor driven plant such as crushers, hoists, conveyors, and borehole pumps runs at a lagging power factor, typically 0.75 to 0.85. Most diesel generator sets and natural gas generator sets are therefore rated at 0.8, which is why this table is the default. A site running at 0.7 needs a 1.43 multiplier instead of 1.25, and that difference alone can push a project into the next frame size.
Frequently Asked Questions
How do I convert kW to kVA?
Divide kW by the power factor. At 0.8 power factor, multiply kW by 1.25. A 1,500 kW load becomes 1,875 kVA.
What happens if I size a generator on kW instead of kVA?
The alternator, cables, breakers, and step up transformer are all rated in kVA. Sizing on kW at 0.8 power factor understates that requirement by 25 percent.
Is 0.8 power factor always correct?
No. It is a rating convention, not a measurement. Confirm the actual site power factor from a load study before committing to a frame size.
Correct kW to kVA conversion is where credible power plant engineering begins. USP&E Global has delivered 150+ projects across 35+ countries and holds equipment across the full range shown above in our live inventory. Reference load and demand data is published by the U.S. Energy Information Administration, the International Energy Agency, and the World Bank.
Ready to Power Your Project? Talk to USP&E’s Engineers Free.
USP&E Global offers a complimentary 4-hour engineering consultation for qualified power station, EPC, and O&M projects. Whether you are in early feasibility or ready to mobilize, our team of 350+ engineers across 35+ countries is ready to guide your project to success with speed and without excuses.
USP&E Global. Powering Possibility. Built for the Frontier.
ISO 9001:2015 | ISO 45001:2018 | 150+ Projects | 35+ Countries | Zero Lawsuits