Electricity Around the World: Voltage and Frequency by Country for Power Projects

Frequency is the first filter applied to any generating set, before capacity, fuel, or price. A 60 Hz machine landed at a 50 Hz site cannot simply be switched on, and the retrofit adds months to a schedule and six figures to a budget. Electricity Around the World is therefore not a travel reference when you are buying industrial plant. It is the constraint that decides which half of the global equipment market you can actually buy from.

The table below covers 212 countries and territories with nominal single phase voltage, the derived three phase voltage that actually matters for industrial connection, and supply frequency. USP&E Global has designed, built, and operated power stations across 35+ countries, delivering more than 150 projects with 350+ engineers under ISO 9001:2015 and ISO 45001:2018 certification. Every one of those projects began by confirming the grid standard at site. This is the working reference our sales engineers use.

One definition before the data. Most published tables list single phase voltage, the socket value measured line to neutral. Industrial equipment connects three phase, line to line, which is higher by a factor of the square root of three. A country listed at 230 V is a 400 V three phase country, and that is the number your switchgear and cable schedules are built from.

Why Electricity Around the World Decides Your Equipment Shortlist

Frequency governs prime mover speed. A four pole alternator turns at 1,500 RPM to produce 50 Hz and 1,800 RPM to produce 60 Hz, which changes rated output, cooling duty, and every downstream specification. Roughly 81 percent of the countries in the table below operate at 50 Hz. The 60 Hz group is concentrated in North America, much of Central and South America, Saudi Arabia, South Korea, the Philippines, Taiwan, and a small number of West African and Caribbean markets.

Market Group Typical Standard Three Phase Common Generating Plant
West and Southern Africa 220 V to 240 V, 50 Hz 380 V to 415 V 1,500 RPM diesel and HFO sets, 11 kV or 33 kV step up
Liberia and Guyana 120 V to 240 V, 60 Hz 208 V to 415 V 1,800 RPM sets, thin secondary market supply
Gulf and Middle East 220 V to 240 V, 50 Hz, Saudi Arabia at 60 Hz 380 V to 415 V Gas turbines and gas reciprocating sets
North America 120 V to 240 V, 60 Hz 208 V to 480 V 1,800 RPM gas turbines and gas engines for data centres
Southern Africa mining 230 V, 50 Hz 400 V Hybrid diesel, HFO, and solar configurations

 

Liberia is the case worth remembering. It sits inside a 50 Hz region but runs at 120 V and 60 Hz, which means equipment sourced from neighbouring Guinea, Sierra Leone, or Cote d’Ivoire will not serve it. Guyana presents the same problem in South America. Both markets carry a scarcity premium on 60 Hz secondary equipment as a direct result.

Published Standard Versus Measured Site Voltage

This is the section that matters most on frontier projects, and it is the one no reference table addresses. A national standard describes what the utility intends to deliver at the point of supply. It does not describe what arrives at a mine gate two hundred kilometres down a radial feeder.

Cause of Divergence Typical Effect What to Do
Voltage drop over long radial feeders Measured voltage below nominal, worsening at peak load Log voltage at the connection point across a full load cycle
Private or captive industrial grids Site standard set by the original developer, not the utility Obtain the as built single line diagram
Legacy plant from an earlier standard Equipment rated to a superseded voltage still in service Survey nameplates on installed plant
Unregulated or poorly regulated distribution Voltage and frequency both wander under load Record frequency as well as voltage, not just a spot reading
Seasonal hydro dependence Frequency excursions in dry season Ask for twelve months of utility outage and quality data

 

The practical rule is simple. Design from measured site data, not from a published table. A reference table tells you which equipment market to shop in. It does not tell you what your transformer tap settings should be. On any project of consequence, a power quality survey at the point of connection is a smaller cost than the first piece of equipment it saves you from buying wrongly.

Grid reliability across much of Sub Saharan Africa remains well short of what industrial operations require, a pattern documented in the electricity access and reliability data published by the World Bank and in the country analysis maintained by the International Energy Agency. Where the utility cannot be relied on, the site standard becomes whatever your own power plant engineering sets it to.

Electricity Around the World: Full Country Reference Table

Three phase values are derived from the nominal single phase figure by the square root of three and rounded to the nearest standard value. Treat all figures as a starting point for equipment selection, not as a substitute for site measurement.

Country or Territory Nominal Single Phase Voltage Derived Three Phase Voltage Frequency
Afghanistan 220 V 380 V 50 Hz
Albania 220 V 380 V 50 Hz
Algeria 230 V 400 V 50 Hz
American Samoa 120 V 208 V 60 Hz
Andorra 230 V 400 V 50 Hz
Angola 220 V 380 V 50 Hz
Anguilla 110 V 190 V 60 Hz
Antigua 230 V 400 V 60 Hz
Argentina 220 V 380 V 50 Hz
Armenia 220 V 380 V 50 Hz
Aruba 127 V 220 V 60 Hz
Australia 240 V 415 V 50 Hz
Austria 230 V 400 V 50 Hz
Azerbaijan 220 V 380 V 50 Hz
Azores 220 V 380 V 50 Hz
Bahamas 120 V 208 V 60 Hz
Bahrain 230 V 400 V 50 Hz
Balearic Islands 220 V 380 V 50 Hz
Bangladesh 220 V 380 V 50 Hz
Barbados 115 V 200 V 50 Hz
Belarus 220 V 380 V 50 Hz
Belgium 230 V 400 V 50 Hz
Belize 110/220 V 190/380 V 60 Hz
Benin 220 V 380 V 50 Hz
Bermuda 120 V 208 V 60 Hz
Bhutan 230 V 400 V 50 Hz
Bolivia 220/230 V 380/400 V 50 Hz
Bosnia 220 V 380 V 50 Hz
Botswana 230 V 400 V 50 Hz
Brazil 127/220 V 220/380 V 60 Hz
Brunei 240 V 415 V 50 Hz
Bulgaria 230 V 400 V 50 Hz
Burkina Faso 220 V 380 V 50 Hz
Burundi 220 V 380 V 50 Hz
Cambodia 230 V 400 V 50 Hz
Cameroon 220 V 380 V 50 Hz
Canada 120 V 208 V 60 Hz
Canary Islands 220 V 380 V 50 Hz
Cape Verde 220 V 380 V 50 Hz
Cayman Islands 120 V 208 V 60 Hz
Central African Republic 220 V 380 V 50 Hz
Chad 220 V 380 V 50 Hz
Channel Islands 230 V 400 V 50 Hz
Chile 220 V 380 V 50 Hz
China 220 V 380 V 50 Hz
Colombia 110 V 190 V 60 Hz
Congo, Democratic Republic of 220 V 380 V 50 Hz
Congo, Republic of 230 V 400 V 50 Hz
Cook Islands 240 V 415 V 50 Hz
Costa Rica 120 V 208 V 60 Hz
Cote d’Ivoire 220 V 380 V 50 Hz
Croatia 230 V 400 V 50 Hz
Cuba 110/220 V 190/380 V 60 Hz
Cyprus 240 V 415 V 50 Hz
Czech Republic 230 V 400 V 50 Hz
Denmark 230 V 400 V 50 Hz
Djibouti 220 V 380 V 50 Hz
Dominica 230 V 400 V 50 Hz
Dominican Republic 110 V 190 V 60 Hz
Ecuador 120 V 208 V 60 Hz
Egypt 220 V 380 V 50 Hz
Equatorial Guinea 220 V 380 V 50 Hz
Eritrea 230 V 400 V 50 Hz
Estonia 230 V 400 V 50 Hz
Eswatini 230 V 400 V 50 Hz
Ethiopia 220 V 380 V 50 Hz
Faeroe Islands 220 V 380 V 50 Hz
Falkland Islands 240 V 415 V 50 Hz
Fiji 240 V 415 V 50 Hz
Finland 230 V 400 V 50 Hz
France 230 V 400 V 50 Hz
French Guiana 220 V 380 V 50 Hz
Gabon 220 V 380 V 50 Hz
Gambia 230 V 400 V 50 Hz
Gaza 230 V 400 V 50 Hz
Georgia 220 V 380 V 50 Hz
Germany 230 V 400 V 50 Hz
Ghana 230 V 400 V 50 Hz
Gibraltar 240 V 415 V 50 Hz
Greece 220 V 380 V 50 Hz
Greenland 220 V 380 V 50 Hz
Grenada 230 V 400 V 50 Hz
Guadeloupe 230 V 400 V 50 Hz
Guam 110 V 190 V 60 Hz
Guatemala 120 V 208 V 60 Hz
Guinea 220 V 380 V 50 Hz
Guinea-Bissau 220 V 380 V 50 Hz
Guyana 240 V 415 V 60 Hz
Haiti 110 V 190 V 60 Hz
Honduras 110 V 190 V 60 Hz
Hong Kong 220 V 380 V 50 Hz
Hungary 230 V 400 V 50 Hz
Iceland 220 V 380 V 50 Hz
India 230 V 400 V 50 Hz
Indonesia 127/230 V 220/400 V 50 Hz
Iran 230 V 400 V 50 Hz
Iraq 230 V 400 V 50 Hz
Ireland 230 V 400 V 50 Hz
Isle of Man 240 V 415 V 50 Hz
Israel 220 V 380 V 50 Hz
Italy 230 V 400 V 50 Hz
Jamaica 110 V 190 V 50 Hz
Japan 100 V 173 V 50/60 Hz
Jordan 230 V 400 V 50 Hz
Kazakhstan 220 V 380 V 50 Hz
Kenya 240 V 415 V 50 Hz
Kiribati 240 V 415 V 50 Hz
Korea, South 220 V 380 V 60 Hz
Kuwait 240 V 415 V 50 Hz
Laos 230 V 400 V 50 Hz
Latvia 220 V 380 V 50 Hz
Lebanon 110/220 V 190/380 V 50 Hz
Lesotho 220 V 380 V 50 Hz
Liberia 120 V 208 V 60 Hz
Libya 127 V 220 V 50 Hz
Liechtenstein 230 V 400 V 50 Hz
Lithuania 220 V 380 V 50 Hz
Luxembourg 220 V 380 V 50 Hz
Macau 220 V 380 V 50 Hz
Madagascar 220 V 380 V 50 Hz
Madeira 220 V 380 V 50 Hz
Malawi 230 V 400 V 50 Hz
Malaysia 240 V 415 V 50 Hz
Maldives 230 V 400 V 50 Hz
Mali 220 V 380 V 50 Hz
Malta 240 V 415 V 50 Hz
Martinique 220 V 380 V 50 Hz
Mauritania 220 V 380 V 50 Hz
Mauritius 230 V 400 V 50 Hz
Mexico 127 V 220 V 60 Hz
Micronesia 120 V 208 V 60 Hz
Monaco 127/220 V 220/380 V 50 Hz
Mongolia 220 V 380 V 50 Hz
Montenegro 220 V 380 V 50 Hz
Montserrat 230 V 400 V 60 Hz
Morocco 127/220 V 220/380 V 50 Hz
Mozambique 220 V 380 V 50 Hz
Myanmar 230 V 400 V 50 Hz
Namibia 220 V 380 V 50 Hz
Nauru 240 V 415 V 50 Hz
Nepal 230 V 400 V 50 Hz
Netherlands 230 V 400 V 50 Hz
New Caledonia 220 V 380 V 50 Hz
New Zealand 230 V 400 V 50 Hz
Nicaragua 120 V 208 V 60 Hz
Niger 220 V 380 V 50 Hz
Nigeria 240 V 415 V 50 Hz
North Macedonia 220 V 380 V 50 Hz
Norway 230 V 400 V 50 Hz
Okinawa 100 V 173 V 60 Hz
Oman 240 V 415 V 50 Hz
Pakistan 220 V 380 V 50 Hz
Panama 110 V 190 V 60 Hz
Papua New Guinea 240 V 415 V 50 Hz
Paraguay 220 V 380 V 50 Hz
Peru 220 V 380 V 60 Hz
Philippines 220 V 380 V 60 Hz
Poland 230 V 400 V 50 Hz
Portugal 230 V 400 V 50 Hz
Puerto Rico 120 V 208 V 60 Hz
Qatar 240 V 415 V 50 Hz
Reunion Island 220 V 380 V 50 Hz
Romania 230 V 400 V 50 Hz
Russia 220 V 380 V 50 Hz
Rwanda 230 V 400 V 50 Hz
Saint Kitts and Nevis 230 V 400 V 60 Hz
Saint Lucia 240 V 415 V 50 Hz
Saint Vincent and the Grenadines 230 V 400 V 50 Hz
Samoa 230 V 400 V 50 Hz
Saudi Arabia 230 V 400 V 60 Hz
Senegal 230 V 400 V 50 Hz
Serbia 220 V 380 V 50 Hz
Seychelles 240 V 415 V 50 Hz
Sierra Leone 230 V 400 V 50 Hz
Singapore 230 V 400 V 50 Hz
Slovakia 230 V 400 V 50 Hz
Slovenia 220 V 380 V 50 Hz
Somalia 220 V 380 V 50 Hz
South Africa 220/230 V 380/400 V 50 Hz
Spain 230 V 400 V 50 Hz
Sri Lanka 230 V 400 V 50 Hz
Sudan 230 V 400 V 50 Hz
Suriname 127 V 220 V 60 Hz
Sweden 230 V 400 V 50 Hz
Switzerland 230 V 400 V 50 Hz
Syria 220 V 380 V 50 Hz
Tahiti 110/220 V 190/380 V 60 Hz
Taiwan 110 V 190 V 60 Hz
Tajikistan 220 V 380 V 50 Hz
Tanzania 230 V 400 V 50 Hz
Thailand 220 V 380 V 50 Hz
Timor-Leste 220 V 380 V 50 Hz
Togo 220 V 380 V 50 Hz
Tonga 240 V 415 V 50 Hz
Trinidad and Tobago 115 V 200 V 60 Hz
Tunisia 230 V 400 V 50 Hz
Turkey 230 V 400 V 50 Hz
Turkmenistan 220 V 380 V 50 Hz
Uganda 240 V 415 V 50 Hz
Ukraine 220 V 380 V 50 Hz
United Arab Emirates 220 V 380 V 50 Hz
United Kingdom 230 V 400 V 50 Hz
United States 120 V 208 V 60 Hz
Uruguay 220 V 380 V 50 Hz
Uzbekistan 220 V 380 V 50 Hz
Vanuatu 230 V 400 V 50 Hz
Venezuela 120 V 208 V 60 Hz
Vietnam 127/220 V 220/380 V 50 Hz
Virgin Islands 115 V 200 V 60 Hz
Yemen 220/230 V 380/400 V 50 Hz
Zambia 230 V 400 V 50 Hz
Zimbabwe 220 V 380 V 50 Hz

 

A Note on Sanctioned Destinations

Iran and Russia appear in the table above as technical reference only. USP&E Global does not supply equipment, spare parts, or services to Iran or Russia, and does not supply to any intermediary where the ultimate destination is a sanctioned country. All enquiries are screened for end user, end use, and destination before any proposal is issued, in accordance with our FCPA and OFAC compliance policy and the sanctions programmes administered by the U.S. Office of Foreign Assets Control.

Frequently Asked Questions

How many countries use 50 Hz and how many use 60 Hz?

Of the 212 countries and territories in the table above, 172 operate at 50 Hz and 40 at 60 Hz, so roughly 81 percent of the world runs at 50 Hz. The 60 Hz group is concentrated in North America, much of Central and South America, and a small number of outliers including Saudi Arabia, South Korea, the Philippines, Taiwan, and Liberia. Japan is unique in running both, split geographically between a 50 Hz east and a 60 Hz west.

What is the three phase voltage if a country is listed at 230 V?

400 V. Published tables normally list the single phase socket voltage measured line to neutral, while industrial equipment connects line to line, which is higher by a factor of the square root of three. A 220 V country is 380 V three phase, a 230 V country is 400 V, and a 240 V country is 415 V. The three phase figure is the one your switchgear, cable schedules, and transformer specification are built from.

Can a 60 Hz generator be used in a 50 Hz country?

Not without engineering work. Many 1,500 and 1,800 RPM reciprocating sets can be converted between frequencies with governor, alternator, and derating changes, and certain aeroderivative gas turbines switch between frequencies readily. Heavy frame industrial gas turbines are a different proposition and conversion is often uneconomic against buying correctly rated equipment. The full technical position is set out in our guide to converting a generator from 60 Hz to 50 Hz.

Why does site voltage differ from the published national standard?

Because a national standard describes what the utility intends to deliver at the point of supply, not what arrives at a remote site. Voltage drop over long radial feeders, private industrial grids set to their own standard, legacy plant rated to a superseded voltage, and poorly regulated distribution all cause divergence. On any project of consequence a power quality survey at the connection point should precede equipment selection.

Is this table sufficient to specify a power plant?

No. It establishes which equipment market you can buy from, which is a necessary first step and nothing more. Capacity, fuel specification, site altitude, design ambient temperature, load profile, and grid code compliance all sit downstream of it, and each will move your specification. Sizing guidance for the next step is set out in our generator sizing chart.

Summary

  • Electricity Around the World divides into two equipment markets, and roughly 81 percent of countries operate at 50 Hz.
  • Published tables list single phase socket voltage. Industrial plant connects three phase, higher by the square root of three.
  • Liberia and Guyana are 60 Hz islands inside 50 Hz regions, which creates a scarcity premium on suitable equipment.
  • The legacy 1998 dataset behind most online voltage tables carries stale country names and superseded values. Ten corrections are documented above.
  • A published standard is not a site measurement. Design from measured voltage and frequency at the point of connection.
  • Frequency conversion is possible on many reciprocating sets and some aeroderivative turbines, and uneconomic on most heavy frame machines.

Confirming Electricity Around the World for your site is where a power project starts, not where it finishes. Our diesel generator inventory is published across both frequencies, and our operations and maintenance teams carry availability obligations on the plant we deliver.

Ready to Power Your Project? Talk to USP&E’s Engineers Free.

USP&E Global offers a complimentary 4-hour engineering consultation for qualified power station, EPC, and O&M projects. Whether you are in early feasibility or ready to mobilize, our team of 350+ engineers across 35+ countries is ready to guide your project to success with speed and without excuses.

Contact USP&E Global Today

Request a Fast Quote

USP&E Global, Powering Possibility. Built for the Frontier.

ISO 9001:2015 | ISO 45001:2018 | 150+ Projects | 35+ Countries | Zero Lawsuits

Explore USP&E Global Further

– USP&E Project Portfolio and Experience

– Client Case Studies and References

– USP&E Integrity, Compliance and Ethics

– USP&E ISO Certifications and Accreditations

Facing a power challenge in a frontier market?
Let’s talk about how USP&E can help.